BE1-87G
Minimum Differential (Operate) Current
0.02, 0.03, 0.04, 0.08, 0.10, 0.16, 0.32 A
Accuracy
For IR 0.8 A: ±5% of operate pickup or ±25 mA
(whichever is greater)
For IR > 1.2 A (4 A max): ±8% of operate pickup or
±150 mA (whichever is greater)
Dropout
> 90% of operate characteristic
Timing
< 30 ms at 10 times pickup setting; 70 ms maximum
Sensing-Range 2