Basler BE1-87G Manual de usuario Pagina 6

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 25
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 5
BE1-87G
Minimum Differential (Operate) Current
0.1, 0.15, 0.2, 0.4, 0.5, 0.8, 1.6 A
Accuracy
For IR 4 A: ±5% of operate pickup or ±25 mA
(whichever is greater)
For IR > 6 A (20 A max.): ±8% of operate pickup or
±150 mA (whichever is greater)
Dropout
> 90% of operate characteristic
Timing
< 30 ms at 10 times pickup setting; 70 ms maximum
Sensing-Range 1
Page 1-5